Air distribution numerical simulating of isothermal jet with interference parameters in large space
Introduction
Environmental quality is directly related to people’s health. In the metal-processing industry, a large amount of fume, smoke and dust, even CO2, HF, O3, are produced during the processing. These contaminants can do great harm to the workers. The steel construction workshop of a bridge girder plant is a typical large workshop, in which the main work is to eliminate rust and polish the surface of steel bridge workpieces. During the process of burnishing, it produces large quantity of dust which can reduce visibility, impede operations, seriously endanger the health of all those around and pollute the environment. In reality, the dust is not easily controlled in large spaces, especially when the dust source is changing and the local exhaust hood can not work effectively. The contaminants may fill the whole space if the distribution of air in building is poor. According to many industry standards, the usual form of ventilation and dust removal in such buildings is general ventilation. However, general ventilation is expensive and may not meet the requirements for environmental protection. The larger building, the greater the volume of air that must be moved for ventilation and the more difficult it is to control dust. So the large workshop with a changeable dust source is paid more and more attention.
The energy-saving and economic method of dust control in large spaces is to reduce the area that needs dust control. An isothermal horizontal jet is applied to divide the space into three parts as shown in Fig. 1. The middle zone is the airflow zone in which the airflow has high velocity and can prevent dust from moving up freely. The lower zone is the control zone which is filled with a great deal of dust that should be exhausted by the ventilation system or using the local exhaust hood. The upper zone is the non-controlled zone, which has little dust if the airflow zone can effectively prevent the dust from moving up.
Multi-parallel jets are different from a single jet because it is the synthesis of several air supplies which leads to the phenomenon of streamline coincidence. Each jet can follow the law of free turbulent jet in the beginning. Soon each jet will be impacted by an adjacent jet, the flow rate will increase and the expansion degree of cross-section will slow down. Then, jet fluid can join with adjacent jet streamlines as is shown in Fig. 2 [1]. Multi-parallel jets can form an air curtain in space and impede contamination.
The characteristics of indoor air distribution are essential to the design of a ventilation system. Efforts have been made to improve numerical prediction techniques for the airflow in rooms. The k–ε turbulence model has been used in the simulation of room airflow with a certain degree of accuracy [2], [3].
This paper takes the steel constructions workshop of a bridge girder plant as an example. Fig. 3 shows a schematic layout of the workshop, which are 63.0 m long, 33.0 m wide and 17.0 m high. The air supply outlets and exhaust outlets were set in the two side walls. The shapes of the workpieces are box, strip, flat plate, etc. The maximum one is 3 × 3 × 40 m.
Section snippets
Simulation model
In order to evaluate the performance of CFD in modeling airflow, the air distribution is simulated in a large space with isothermal jets and results of the simulation are validated by the experimental formula. The main purpose is to investigate the effects of some factors on air distribution in large spaces, such as the height of air supply outlets and exhaust outlets, height and location of barrier, etc. This paper is not particularly interested in the boundary layer, except as it affects the
Results
The simulated cases are shown as case 1 to case 5.Case 1 Case 2 Mode: one-side air supply and one-side exhaust Mode: one-side air supply and one-side exhaust Supply outlet: rectangle (0.5 × 1 m), number: 6 Supply outlet: circle (0.5 × 0.5 m), number: 10 Exhaust outlet: rectangle (0.5 × 3 m), number: 4 Exhaust outlet: rectangle (0.5 × 3 m), number: 4 Height of supply outlet: 6 m Height of supply outlet: 6 m Jet velocity: 6 m/s Jet velocity: 4.5 m/s Barrier: none Variable: height of exhaust outlet Barrier: none Case 3 Case 4
Conclusion
Based on this study, the following conclusions are obtained:
- 1.
The method of stratified ventilation can be used to get good air distribution in large spaces with a changeable dust source.
- 2.
Compared with general ventilation, the stratified ventilation can reduce the initial costs and operation cost. There are two important factors to evaluate air distribution in large spaces with a changeable dust source. One is the velocity of airflow that should be large enough to prevent dust from entering the
References (19)
- et al.
CFD analysis on characteristics of contaminated indoor air ventilation and its application in the evaluation of the effects of contaminant inhalation by a human occupant
Building and Environment
(2002) - et al.
The numerical computation of turbulence flows
Computer Methods in Applied Mechanics and Engineering
(1974) Heating and Ventilation Handbook
(1987)- et al.
CFD analysis and energy simulation of a gymnasium
Building and Environment
(2001) Numerical Heat Transfer
(1988)- et al.
Numerical simulation of the high Reynolds number slit nozzle gas-particle jet using subgrid-scale coupling large eddy simulation
Chemical Engineering Science
(2001) - et al.
A comparative study of room airflow: numerical prediction using computational fluid dynamics and full-scale experimental measurements
ASHRAE Transaction
(1993) - et al.
Comparison of numerical predictions of horizontal nonisothermal jet in a room with three turbulence models—k–ε EVM, ASM, AND DSM
ASHRAE Transaction
(1994) - et al.
Mathematical Models of Turbulence
(1972)
Cited by (14)
Experimental study on the characteristics of secondary airflow device in a large enclosed space building
2018, Energy and BuildingsCitation Excerpt :In addition, air-conditioning system of a large space building relies on supply air terminals such as nozzles and diffusers to deliver primary conditioned air, but parking garage and traffic tunnel does not necessarily have well organized supply air, which can be exhaust resultant (for garage) or infiltration from opening (tunnel). For large space buildings, conditioned air supplied [19] by a regular air distributor, such as side-wall air supply nozzle, can be passed along to the induction fan system that performs as secondary airflow relay [20] to enhance the movement of indoor air near the occupied zone. The secondary airflow will help provide extra momentum [21] to the supplied air as well as help disperse and remove contaminant in occupied space.
The Research of the Characteristics of Secondary Equipment Device and Airflow Jet
2015, Procedia EngineeringDesign configuration for a higher efficiency air conditioning system in large space building
2014, Energy and BuildingsCitation Excerpt :In 1979, the Chinese Academy of Sciences organized its second, sixth and seventh Design Institute of Ministry of Machinery and other design institutes to participate in the study of the stratified air conditioning design in large workshops and had many important achievements [10]. After the 1990s, with the development of construction technology, more large space buildings were emerging in China, and the study of temperature and air flow distribution has received even more attention since then [11–13]. To the best of our knowledge, there are two kinds of methods for investigating the stratified air conditioning design.
Optimization of ventilation performance of side air supply for large indoor spaces using deflectors and slot air outlets
2023, Indoor and Built Environment