Title: Non-Intrusive Load Monitoring of HVAC Components using Signal Unmixing

Conference ·
OSTI ID:1265590

Heating, Ventilating and Air Conditioning units (HVAC) are a major electrical energy consumer in buildings. Monitoring of the operation and energy consumption of HVAC would increase the awareness of building owners and maintenance service providers of the condition and quality of performance of these units, enabling conditioned-based maintenance which would help achieving higher energy efficiency. In this paper, a novel non-intrusive load monitoring method based on group constrained non-negative matrix factorization is proposed for monitoring the different components of HVAC unit by only measuring the whole building aggregated power signal. At the first level of this hierarchical approach, power consumption of the building is decomposed to energy consumption of the HVAC unit and all the other electrical devices operating in the building such as lighting and plug loads. Then, the estimated power signal of the HVAC is used for estimating the power consumption profile of the HVAC major electrical loads such as compressors, condenser fans and indoor blower. Experiments conducted on real data collected from a building testbed maintained at the Oak Ridge National Laboratory (ORNL) demonstrate high accuracy on the disaggregation task.

Research Organization:
Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States). Building Technologies Research and Integration Center (BTRIC)
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE)
DOE Contract Number:
AC05-00OR22725
OSTI ID:
1265590
Resource Relation:
Conference: 3rd IEEE Global Conference on Signal and Information Processing, 1st International Symposium on Signal Processing Applications in Smart Buildings, Orlando, FL, USA, 20151214, 20151216
Country of Publication:
United States
Language:
English

Similar Records

Non-Intrusive Energy Disaggregation Using Non-Negative Matrix Factorization With Sum-to-k Constraint
Journal Article · Thu Jan 26 00:00:00 EST 2017 · IEEE Transactions on Power Systems · OSTI ID:1265590

HVAC load Disaggregation using Low-resolution Smart Meter Data
Conference · Fri Feb 01 00:00:00 EST 2019 · 2019 IEEE Power & Energy Society Innovative Smart Grid Technologies Conference (ISGT) · OSTI ID:1265590

What are the Impacts on the HVAC System when it Provides Frequency Regulation? – A Comprehensive Case Study with a Multi-Zone Variable Air Volume (VAV) System
Journal Article · Thu Jul 15 00:00:00 EDT 2021 · Energy and Buildings · OSTI ID:1265590