Abstract:
This paper analyzes the behavior of a Voltage Source Converter Based HVDC system under DC cable fault conditions. The behavior of the HVDC system during a permanent line-...Show MoreMetadata
Abstract:
This paper analyzes the behavior of a Voltage Source Converter Based HVDC system under DC cable fault conditions. The behavior of the HVDC system during a permanent line-to-earth fault is analyzed, outlining the systems configuration and behavior at each stage of the fault timeline. Operation of the proposed system under a single earthing configurations i.e. Converter (solid) earthed/AC transformer unearthed, was analyzed and simulated, with particular attention paid to the converters operation. It was observed that the development of potential earth loops within the system as a result of DC line-to-earth faults leads to substantial overcurrent and results in system configuration oscillation.
Date of Conference: 10-13 November 2013
Date Added to IEEE Xplore: 02 January 2014
Electronic ISBN:978-1-4799-0224-8
Print ISSN: 1553-572X