Abstract:
Line protection in HV/EHV/UHV lines is primarily by distance protection due to its selective, reliable and secure operation. With the wind farm penetration, the SIRs of l...Show MoreMetadata
Abstract:
Line protection in HV/EHV/UHV lines is primarily by distance protection due to its selective, reliable and secure operation. With the wind farm penetration, the SIRs of lines are going to change drastically throughout the day. A case study has been performed in this paper to study the behavior of dynamic characteristics with respect to these changes. Analytically fault voltages and currents are calculated for the system. Distance relay implemented on hardware has been validated with these waveforms and inferences have been made to give recommendations for characteristics to be applied in practical systems for secure and reliable operation of distance relay.
Date of Conference: 03-06 November 2015
Date Added to IEEE Xplore: 21 January 2016
ISBN Information:
Electronic ISSN: 2378-8542