Abstract:
In this work, a ten year gas production records, obtained from Rodgers ratio codes for gas concentration of H2, CH4, C2H6, C2H4 and C2H2, in a 795 MVA 20/400 kV rated pow...Show MoreMetadata
Abstract:
In this work, a ten year gas production records, obtained from Rodgers ratio codes for gas concentration of H2, CH4, C2H6, C2H4 and C2H2, in a 795 MVA 20/400 kV rated power transformer are used in MLP for improving the diagnosis accuracy of incipient faults (partial discharge, thermal faults, low and high energy discharges, etc...). Numerical modelling of DGA-sourced data was achieved using MATLAB platform. Performance validation for the neural network was assessed in terms of the regression fit (R), the MSE and the MAPE. Results show 2.51 % as optimal value of MAPE which indicate a reasonable accuracy of ANN technique in the prediction of incipient faults.
Date of Conference: 12-14 June 2019
Date Added to IEEE Xplore: 01 August 2019
ISBN Information: