The cascaded H-bridge (CHB) static synchronous compensator (STATCOM) has been widely used in wind farm and conflux station. As the grid-connected voltage increases, the n...Show MoreMetadata
Abstract:
The cascaded H-bridge (CHB) static synchronous compensator (STATCOM) has been widely used in wind farm and conflux station. As the grid-connected voltage increases, the number of CHB proportionately increases. In order to achieve the capacitor voltage balance, it is necessary to independently detect the capacitor voltage of all H-bridge cells, which raises the cost of capacitor voltage detection. To solve this problem, the mapping relationship is studied between the converter output voltage and capacitor voltages by analyzing carrier phase-shifted sinusoidal pulse width modulation technique, and special switching mode is first found. Based on the abovementioned finding, without changing the conventional CHB topology, an improved sensorless detection method is proposed to solve the problems of detection error, large computation burden, and the application limitation in existing sensorless detection methods. Compared with conventional sensor detection, this method not only saves dc voltage sensors and data transmission channels but also suppress the third harmonics in the converter current. Finally, the effectiveness of the detection method applied on CHB STATCOM is proved by simulation and experiment.
Published in: IEEE Transactions on Industrial Electronics ( Volume: 70, Issue: 12, December 2023)