Innovation-section: test-run for uprating a 220 kV OHL to 380 kV using insulated cross-arms and coated conductors

  • CIGRE 2016
  • Published:
e & i Elektrotechnik und Informationstechnik Aims and scope Submit manuscript

Abstract

Different approaches to strengthen the transmission network for increasing load flows are used. One strategic principle is the “optimization before extension”, which means applying methods which make comprehensive reconstructions redundant. A possibility to increase the capacity of an existing overhead line is the uprating of the voltage level. Such a voltage uprate – using existing assets and not requiring a new line corridor – is cost- and time efficient and gains more public acceptance. The challenge is that the increased voltage level causes higher electric fields resulting in possibly higher corona noise.

The paper presents the solutions and innovations that were developed and tested to uprate an existing 220 kV overhead line (OHL) to 380 kV. In the project called “innovation-section“ methods for uprating lines from 220 kV to 380 kV are implemented. This “innovation-section” is a 1,2 km long part of an existing 380 kV line in Austria, with three suspension towers. The section is being used for a test-run of two technical innovations which are newly developed insulated cross-arms and conductors with a special construction and a treated surface.

When uprating from 220 kV to 380 kV the existing ton-style lattice steel towers has to be converted to a new type of tower ensuring the clearances which are needed for the higher voltage level. The solution is an insulated cross-arm. In contrast to the well-known standard lattice steel cross arm in combination with suspension strings, insulators are directly connected to the tower’s body as horizontal Vee. The new suspension was mechanically and electrically type tested with a special focus on low corona extinction voltage.

As audible noise (AN) is one of the main aspects when increasing voltage, new conductors were developed to reduce corona noise. Special measures are taken to increase the diameter of the new conductors, without increasing mechanical forces on the existing towers and keeping the same current capacity. Moreover, a hydrophilic coating is applied. According to first laboratory test results a noise reduction of approx. 10 dB(A) is expected compared to untreated standard conductors.

The components which are necessary for the uprating have been developed and tested successfully.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Fig. 1.
Fig. 2.
Fig. 3.
Fig. 4.
Fig. 5.
Fig. 6.
Fig. 7.

References

  1. Baker, A. C. (2013): High voltage braced insulator assemblies strength requirements. In INMR World Congress 2013, Vancouver.

    Google Scholar 

  2. Phillips, A. J., Maxwell, A. J., Engelbrecht, C. S., Gutman, I. (2015): Electric-field limits for the design of grading rings for composite line insulators. IEEE Trans. Power Deliv., 30(3), 1110.

    Article  Google Scholar 

  3. Baker, A. C., Bernstdorf, R. A., del Bello, E., Hill, R. J., King, B., Philips, A. J., Powell, D. G., Shaffner, D., Steward, G. A., Grisham, T. (2008): EE guide for braced insulator assemblies for overhead transmission lines 60 kV and greater. IEEE Trans. Power Deliv., 23(2), 785–791.

    Article  Google Scholar 

  4. Papailiou, K. O., Schmuck, F. (2012): Silicone composite insulators: materials, design, applications. Berlin: Springer. ISBN-13 978-3642153198.

    Google Scholar 

  5. IEC62567:2013 “Overhead lines – methods for testing self-damping characteristics of conductors”.

  6. Babuder, M., Kobal, I. (2011): Recognition of corona discharges occurring on the wet surface of high-voltage OHL phase conductors. In XVII international symposium on high voltage engineering, Hannover, August 2011.

    Google Scholar 

  7. Becan, M., Babuder, M., Vizintin, S., Kobal, I. (2016): Corona performance of 400 kV bundle conductors and insulator strings. In CIGRE Session 2016, Paris, B2-112.

    Google Scholar 

  8. Schichler, U., Woschitz, R., Pirker, A., Reich, K., Leonhardsberger, M., Oberzaucher, O. (2016): Audible noise performance of OHL conductor bundles. In CIGRE SEERC Power Conference, Portoroz, June 2016 (pp. 4–13).

    Google Scholar 

Download references

Author information

Authors and Affiliations

Authors

Corresponding author

Correspondence to Klemens Reich.

Additional information

Paper submitted for the CIGRE Session 2016, SC B2, Paris, France, August 21–26, 2016.

Rights and permissions

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Schichler, U., Hadinger, N., Troppauer, W. et al. Innovation-section: test-run for uprating a 220 kV OHL to 380 kV using insulated cross-arms and coated conductors. Elektrotech. Inftech. 134, 46–52 (2017). https://doi.org/10.1007/s00502-016-0449-z

Download citation

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s00502-016-0449-z

Keywords

Navigation