Abstract
In 2010, the Addendum D to ASHRAE Standard 170, “Ventilation of healthcare facilities,” lowered the minimum relative humidity (RH) requirement of anesthetizing locations (including operating rooms, operating/surgical cystoscopic rooms, delivery rooms (Caesarean), recovery rooms, critical and intensive care, newborn intensive care, treatment rooms, trauma rooms (crisis or shock), laser eye rooms, newborn nursery suites, and endoscopy rooms) from 30 % to 20 %. The new minimum limit was adopted based on the results of a review paper that suggested that lowering humidity levels will have little or no impact on providing a safe environment for patients, staff, or medical equipment. That review paper reached this conclusion by assuming that there were no medical device failures due to electrostatic discharge (ESD). However, in an examination of the FDA’s MAUDE database of reported defects and recalls, we identified numerous medical device failures explicitly due to ESD. This paper presents technical reliability and safety concerns regarding the new guidelines and recommends that such changes should not be implemented and that the guidelines should be revoked.
Access this article
We’re sorry, something doesn't seem to be working properly.
Please try refreshing the page. If that doesn't work, please contact support so we can address the problem.




Similar content being viewed by others
References
ISO 13485: Medical devices - Quality management systems - Requirements for regulatory purposes. ISO, 2003
IEC 60601-1, “Medical electrical equipment – Part 1: General requirements for basic safety and essential performance, Teminology and Definitions.” International Electrotechnical Commission, Genova, 2005.
Food and Drug Administration, “Electromagnetic compatibility aspects of medical device quality systems,” Electromagnetic Compatibility. [Online]. Available: http://www.fda.gov/ICECI/Inspections/InspectionGuides/ucm090595.htm. [Accessed: 03-Jun-2015]
T. Dangelmayer, “Fundamentals of electrostatics,” in ESD Program Management: A Realistic Approach to Continuous Measurable Improvement in Static Control, Springer Science & Business Media, 2012.
IEC 60601-1-2, “Medical electrical equipment — Part 1–2: General requirements for basic safety and essential performance — Collateral standard: Electromagnetic compatibility — Requirements and tests.” International Electrotechnical Commission, Genova, 2014.
U. S. Food and drug administration, Center for Devices and Radiological Health, “Radio Frequency Wireless Technology in Medical Devices- Guidance for Industry and Food and Drug Administration Staff.” [Online]. Available: http://www.fda.gov/RegulatoryInformation/Guidances/ucm077210.htm. [Accessed: 08-Jun-2015]
Dai, J., Das, D., and Pecht, M., Prognostics-based risk mitigation for telecom equipment under free air cooling conditions. Appl. Energy. 99:423–429, 2012.
Paasi, J., Nurmi, S., Vuorinen, R., Strengell, S., and Maijala, P., Performance of ESD protective materials at low relative humidity. J. Electrost. 51–52:429–434, 2001.
Thomas, G.J., Fire and explosion hazards with flammable anesthetics and their control. J. Natl. Med. Assoc. 52(6):397–403, 1960.
F. Memarzadeh. Literature review of the effect of temperature and humidity on viruses. ASHRAE Trans., vol. 117, no. 2, 2011
HVAC Design Manual for New, Replacement, Addition, and Renovation of Existing VA Facilities. Office of Construction & Facilities Management, Department of Veterans Affairs, 2011
IEC 61000-4-2. Electromagnetic compatibility (EMC)- Part 4–2: Testing and measurement techniques - Electrostatic discharge immunity test. International Electrotechnical Commission, Genova
T. Viheriakoski, M. Kokkonen, P. Tamminen, E. Karja, J. Hillberg, and J. Smallwood. Electrostatic threats in hospital environment. in 36th Electrical Overstress/Electrostatic Discharge Symposium (EOS/ESD), 2014, pp. 1–9
M. Moradian, A. Patnaik, Y. Han, F. Wan, D. Pommerenke, and D. Swensen. Determination of the effect of humidity on the probability of ESD failure or upset in data centers. ASHRAE Trans., vol. 120, no. 2, 2014
Acknowledgments
The authors would like to thank the more than 100 companies and organizations that support research activities at the Center for Advanced Life Cycle Engineering (CALCE) at the University of Maryland annually. The authors would especially like to thank Mr. Jeffrey Silberberg and Mr. Sandy Weininger from the FDA’s Center for Devices and Radiological Health, Mr. Andrew Streifel from ASHRAE 170 Standard Committee, and Mr. Jay Hamlin from Medtronic Microelectronics Center, for their time and invaluable assistance, helpful suggestions, and critiques. The research reported herein was partially supported by the NSFC under grant number 71420107023, 71231001 and 71301009.
Author information
Authors and Affiliations
Corresponding author
Ethics declarations
Conflicts of Interests
Authors declare no conflicts of interests.
Additional information
This article is part of the Topical Collection on Systems-Level Quality Improvement
Rights and permissions
About this article
Cite this article
Kohani, M., Pecht, M. New Minimum Relative Humidity Requirements Are Expected to Lead to More Medical Device Failures. J Med Syst 40, 58 (2016). https://doi.org/10.1007/s10916-015-0421-1
Received:
Accepted:
Published:
DOI: https://doi.org/10.1007/s10916-015-0421-1