ABSTRACT
Dissolved gases in oil analysis has been a significant conventional condition detection method for condition evaluation for power transformers. But false data and wrong data do exist in DGA on-line monitoring system, which often lead to misjudgment. To handle this problem, the monitoring system often uses a threshold method based on data distribution statistics to determine the authenticity of the data. However, it is difficult to grasp the rules of the data distribution in advance, resulting in the problem of generally low detection rate of abnormal data. In this paper, according to the time series characteristics of on-line monitoring data of DGA, an abnormal data detection method based on condensed hierarchical clustering is proposed. First, the sliding time window is used to preprocess a variety of oil gas monitoring data to obtain a time series set of monitoring data, and comprehensively apply statistical indicators to classify them and establish Typical time series map; on this basis, the agglomerated hierarchical clustering model is used to perform similarity clustering on the distance between different characteristic data points and the typical abnormal map to determine the abnormal type of the monitoring data. The verification of the application of actual monitoring data shows that this method can detect data anomalies in the online monitoring data stream and determine its type in real time.
- C Guo, B Wang, Z Wu, M. Dong, IET GENER TRANSM DI, 14(11): 2202-2208 (2020).Google ScholarCross Ref
- M. Dong, B. Wang, M. Ren, IEEE Trans. Power Deliv, 34(4), 1221-1229, (2019).Google ScholarCross Ref
- B Wang, M Dong, M Ren, Z Wu, C Guo, T Zhuang, O Pischler, J Xie, IEEE TIM, 69(8), 5345–5355 (2020).Google Scholar
- Y Liang, K Li, Proceedings of the CSEE, 34 (9):1446-1453. (2014).Google Scholar
- Y YAN, G SHENG, Y LIU, X DU, H WANG, X JIANG, High Voltage Technology, 42(12): 4020-4025 (2016).Google Scholar
- B QI, P ZHANG, Z RONG , Power System Technology, 41(11): 275-282 (2017).Google Scholar
- H LIU, J ZHANG, H LIAN High Voltage Apparatus, 55(12): 193-199 (2019).Google Scholar
- T CHEN, Z ZHENG, J LOU, High Voltage Apparatus, 55(08): 164-170 (2019).Google Scholar
- T Fu, ENG APPL ARTIF INTEL, 24(1):164-181 (2011).Google ScholarDigital Library
Recommendations
An anomaly detection approach for multiple monitoring data series based on latent correlation probabilistic model
Condition monitoring systems are widely used to monitor the working condition of equipment, generating a vast amount and variety of monitoring data in the process. The main task of surveillance focuses on detecting anomalies in these routinely collected ...
Anomaly and change point detection for time series with concept drift
AbstractAnomaly detection is one of the most important research contents in time series data analysis, which is widely used in many fields. In real world, the environment is usually dynamically changing, and the distribution of data changes over time, ...
The Research and Application of the On-line Monitoring Technology to the Dissolved Gases in Transformer Oil
ICECC '12: Proceedings of the 2012 International Conference on Electronics, Communications and ControlThe detection and analysis of gases dissolved in transformer oil is an effective method to determine the transformer's internal insulating condition and the type of fault. Because of the large measurement error of the existing off-line test method and ...
Comments